5808011-JIM-A-0320
Johnson Controls Ducted Systems 27
J06-12ZB Standard Indoor Blower - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
MCA
1
w/Pwr
Exh
(Amps)
Max fuse
2
/
breaker
3
size
(amps)
Max Fuse
2
/
Breaker
3
Size w/
Pwr Exh
(Amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps
J06
(6.5)
208-3-60 9.6 73.8 15 3.03 4.9 5.5
None - - - 37.5 43 50 50
E09 6.8 1 18.9 37.5 43 50 50
E18 13.5 2 37.5 53 59.9 60 60
E24 18 2 50 68.6 75.5 70 80
E36 25.5 2 70.8 94.6 101.5 100 110
230-3-60 9.6 73.8 15 3.03 4.9 5.5
None - - - 37.5 43 50 50
E09 9 1 21.7 37.5 43 50 50
E18 18 2 43.3 60.3 67.1 70 70
E24 24 2 57.7 78.3 85.1 80 90
E36 34 2 81.8 108.4 115.3 110 125
460-3-60 5.1 37 8 1.6 2.4 2.2
None - - - 18.2 20.4 20 25
E09 9 1 10.8 18.2 20.4 20 25
E18 18 2 21.7 30.1 32.9 35 35
E24 24 2 28.9 39.1 41.9 40 45
E36 34 2 40.9 54.1 56.9 60 60
575-3-60 3.2 26 5 1.35 2.1 1.8
None - - - 14.1 15.9 15 20
E09 9 1 8.7 14.1 15.9 15 20
E18 18 2 17.3 24.3 26.5 25 30
E24 24 2 23.1 31.5 33.8 35 35
E36 34 2 32.7 43.5 45.8 45 50
J07
(7.5)
208-3-60 14 83.1 22 3.03 4.9 5.5
None - - - 42.1 47.6 50 60
E09 6.8 1 18.9 42.1 47.6 50 60
E18 13.5 2 37.5 53 59.9 60 60
E24 18 2 50 68.6 75.5 70 80
E36 25.5 2 70.8 94.6 101.5 100 110
230-3-60 14 83.1 22 3.03 4.9 5.5
None - - - 42.1 47.6 50 60
E09 9 1 21.7 42.1 47.6 50 60
E18 18 2 43.3 60.3 67.1 70 70
E24 24 2 57.7 78.3 85.1 80 90
E36 34 2 81.8 108.4 115.3 110 125
460-3-60 6.4 41 10 1.6 2.4 2.2
None - - - 19.7 21.9 25 25
E09 9 1 10.8 19.7 21.9 25 25
E18 18 2 21.7 30.1 32.9 35 35
E24 24 2 28.9 39.1 41.9 40 45
E36 34 2 40.9 54.1 56.9 60 60
575-3-60 4.6 33 7 1.35 2.1 1.8
None - - - 14.8 16.6 15 20
E09 9 1 8.7 14.8 16.6 15 20
E18 18 2 17.3 24.3 26.5 25 30
E24 24 2 23.1 31.5 33.8 35 35
E36 34 2 32.7 43.5 45.8 45 50