Hardware Installation—IFC-200 Hardware Installation Procedures 21
Shield Termination in No Conduit (Figure 13)
● Do not allow the SLC shield drain wire to enter the system cabinet.
● Connect the drain wire to the outside of the cabinet via a BX-type
connector.
Shield Drain Wire
Shield
IFC-200 Cabinet
SLC
+
SLC
-
BX Connector
Figure 13: Shield Termination in No Conduit
Shield Termination in Full Conduit (Figure 14)
● The shield drain wire must be connected to the negative (-) side of the
loop.
● Do not allow the shield drain wire or the shield foil to touch the system
cabinet.
Note: For Style 6 or Style 7 field wiring of the SLC loop, connect each
end of the shield to the negative side of the respective SLC.
Shield.drw
Shield Drain
Wire
IFC-200 Cabinet
The shield must not be connected to
earth gournd at any point.
SLC
+
SLC
-
Figure 14: Shield Termination in Full Conduit
SLC Shield
Termination