Hardware Installation—IFC-200 Hardware Installation Procedures 21
Shield Termination in No Conduit (Figure 13)
Do not allow the SLC shield drain wire to enter the system cabinet.
Connect the drain wire to the outside of the cabinet via a BX-type
connector.
Shield Drain Wire
Shield
IFC-200 Cabinet
SLC
+
SLC
-
BX Connector
Figure 13: Shield Termination in No Conduit
Shield Termination in Full Conduit (Figure 14)
The shield drain wire must be connected to the negative (-) side of the
loop.
Do not allow the shield drain wire or the shield foil to touch the system
cabinet.
Note: For Style 6 or Style 7 field wiring of the SLC loop, connect each
end of the shield to the negative side of the respective SLC.
Shield.drw
Shield Drain
Wire
IFC-200 Cabinet
The shield must not be connected to
earth gournd at any point.
SLC
+
SLC
-
Figure 14: Shield Termination in Full Conduit
SLC Shield