Hardware Installation—IFC-200 Hardware Installation Procedures 37
Standoffs Standoffs
Main Board
Main Board
Use metal screw and
standoff here.
Insert screw here.
RTM-8 Option Board
4XTM Option Board
FIG2-22
Figure 29: Optional Module Installation
FIG2-23
4XTM
4XTM Transmitter Module (Activated Polarities Shown)
1
2
3
4
5
6
+
-
+
-
+
-
Remote Alarm
Remote Trouble
Municipal Box
TBL Jumper
Disconnect LED
Disconnect Switch
Figure 30: 4XTM Transmitter Module
(Polarities Shown in Activated Positions)
1. Push the disconnect switch down to prevent unwanted activation of the
municipal box during testing of the control panel.
The Disconnect LED will remain illuminated while the municipal box is
disconnected. The System Trouble LED will indicate disconnected and/or
open circuit conditions on the municipal box.
2. Cut the TBL jumper if you want an open condition during Alarm
Reverse-Polarity output operation.