Table 92: Master slot numbers
Slot number Description
21006 Position Z12
21010 Current V1
21011 Current V2
21012 Current V3
21013 Current V4
21014 Current W1
21015 Current W2
21016 Current W3
21017 Current W4
21018 Current Z1A
21019 Current Z2A
21020 Z1 Temperature
21021 Z2 Temperature
21022 MBC Amplifier Temp
21024 Rotor Elongation
21025 Motor Speed
21041 MBC Fault
21042 First Alarm Code
21043 Rotation Allowed
21045 Control Mode
21072 VW13 Soft Landing Counter
21073 VW24 Soft Landing Counter
21074 Z12 Soft Landing Counter
21075 VW13 Hard Landing Counter
21076 VW24 Hard Landing Counter
21077 Z12 Hard Landing Counter
21049 A13 Unbalance
21050 B13 Unbalance
21051 A24 Unbalance
21052 B24 Unbalance
21053 Az Vibration
21054 Bz Vibration
21078 SDR Counter
21079 MBC Input Voltage
21154 MBC Max Alarm Level
21055 MBC Alive
21152 MBC Levitation Command
21153 MBC Rotation Command
21155 MBC Shutdown Request
Power panel
17940 Control Voltage
17938 Power Loss Time
17941 UPS Line / Charging
17942 UPS Inverter
17943 UPS Fault
17950 UPS Battery Voltage
17948 UPS Inverter Enable
17937 Power Panel Cooling Threshold
17939 Power Panel Temperature
17947 Power Panel Cooling System Run
93
YMC
2
Mod B with OptiView Control Center