Table 86: ZY08 Charging Table System 2
Air Flow Indoor Db/Wb Outdoor DB Suction P Suction Temp. Liquid P Liquid Temp. Delta T Db Compr. amps
75 140 59 264 81 -25 6.9
85 140 58 316 89 -26 7.9300 Cfm/Ton 80/62
95 139 56 368 97 -27 8.9
75 141 59 264 81 -25 6.9
85 145 59 314 90 -24 7.8300 Cfm/Ton 80/67
95 148 59 364 100 -23 8.8
75 142 58 264 81 -25 6.9
85 150 60 312 92 -23 7.8300 Cfm/Ton 80/72
95 157 61 361 102 -20 8.6
75 134 56 265 79 -23 6.9
85 135 56 317 88 -23 7.9300 Cfm/Ton 75/62
95 137 55 369 97 -23 8.9
75 144 61 265 81 -23 6.9
85 147 61 316 90 -23 7.9400 Cfm/Ton 80/62
95 149 60 367 99 -23 8.8
75 147 62 264 82 -23 6.9
85 150 61 314 92 -22 7.8400 Cfm/Ton 80/67
95 153 60 365 101 -21 8.8
75 149 62 263 84 -22 6.9
85 153 61 312 93 -21 7.8400 Cfm/Ton 80/72
95 158 61 362 102 -19 8.7
75 139 58 265 80 -21 6.9
85 142 58 317 89 -20 7.9
400 Cfm/Ton 75/62
95 144 58 369 98 -19 8.9
Table 87: ZY09 Charging Table System 1
Air Flow Indoor Db/Wb Outdoor DB Suction P Suction Temp. Liquid P Liquid Temp. Delta T Db Compr. amps
75 138 63 278 79 -26 7.7
85 138 61 325 89 -27 8.5300 Cfm/Ton 80/62
95 137 59 371 98 -27 9.3
75 137 62 277 80 -26 7.6
85 141 62 325 89 -25 8.5300 Cfm/Ton 80/67
95 144 62 374 98 -24 9.3
75 137 61 275 80 -27 7.6
85 144 63 325 90 -24 8.5300 Cfm/Ton 80/72
95 151 64 376 99 -21 9.3
75 132 60 277 78 -24 7.6
85 133 58 325 88 -23 8.5300 Cfm/Ton 75/62
95 134 57 372 97 -23 9.4
75 142 66 281 79 -23 7.7
85 144 64 327 89 -23 8.5400 Cfm/Ton 80/62
95 146 63 374 99 -23 9.4
75 143 65 279 80 -23 7.7
85 147 64 327 90 -22 8.5400 Cfm/Ton 80/67
95 150 64 375 99 -21 9.4
75 144 64 278 81 -23 7.7
85 149 64 327 90 -21 8.5400 Cfm/Ton 80/72
95 155 65 376 99 -20 9.3
75 137 62 280 79 -21 7.7
85 139 61 327 88 -20 8.5
400 Cfm/Ton 75/62
95 141 61 375 98 -20 9.4
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A 135
Johnson Controls Ducted Systems