8. Troubleshooting
JCY-1800/1850 VDR/S-VDR Installation Guide
112
DOC No. 7ZPJD0387C
Symptom Causes Actions to be taken
Faulty wiring between the Remote Maintenance
Board and the Main Control Board
Check the wiring between the Remote
Maintenance Board and the Main Control
Board.
Check the LAN communication by a PING
command.
MCB: PING 192.168.110.3
FGB: PING 192.168.60.3
In case a no response
MCB (CDJ-2304) :
Fault in a circuit board or setting data
RMB (CDK-287) :
Fault in a circuit board or setting data
ERROR CODE: “80__”
lights up.
Fault in the Remote Maintenance Board
Fault in the Main Control Board
Reboot the Recording Control Unit, and see if
the symptom persists
or not. If yes, contact
us.
RMB (CDK-287) :
Fault in a circuit board or setting data
Exchange the RMB.
ERROR CODE: “81__”
lights up.
Fault in the Remote Maintenance Board Reboot the Recording Control Unit, and see if
the symptom persists or not. If yes, contact
us.
RMB (CDK-287) :
Fault in a circuit board or setting data
Exchange the RMB.