Figure 140: Proper Load Balancing for JNP10K-PWR-DC2 Power Cables on MX100016
g100690
WARNING: Ensure that the power cords do not block access to router components
or drape where people can trip on them.
18. Set the three dip switches to set the inputs and whether the power supply is running at 3000 W,
5000 W, or 5500 W. See Table 58 on page 242 and Figure 141 on page 243.
Set both enable routers to the on position when using both source inputs. When not using source
redundancy, set the unused source to the O (off) position. The LED turns red and indicates an error if
a source input is not in use and the enable router is | (on).
Table 58: Setting the JNP10K-PWR-DC2 Dip Switches
FieldStateSwitch
IP0 is presentOn1
IP0 is not presentOff
IP1 is presentOn2
IP1 is not presentOff
242