Table 27: QFX5200 Switch Environmental Tolerances
(Connued)
Descripon Model Tolerance
Temperature QFX5200-32C and
QFX5200-32C-L
Normal operaon ensured in temperature range
of 32° F through 104° F (0° C through 40° C)
Nonoperang storage temperature in shipping
container: –40° F through 158° F (–40° C
through 70° C)
QFX5200-48Y
Normal operaon ensured in temperature range
of 32° F through 113° F (0° C through 45° C) for
AFO models, 32° F through 104° F (0° C
through 40° C) for AFI models
Nonoperang storage temperature in shipping
container: –40° F through 158° F (–40° C
through 70° C) for both AFO and AFI
Seismic QFX5200 all models Designed to comply with Zone 4 earthquake
requirements per NEBS GR-63-CORE, Issue 3.
NOTE: Install QFX Series devices only in restricted areas, such as dedicated equipment rooms
and equipment closets, in accordance with Arcles 110-16, 110-17, and 110-18 of the Naonal
Electrical Code, ANSI/NFPA 70.
General Site Guidelines
Ecient device operaon requires proper site planning and maintenance and proper layout of the
equipment, rack or cabinet, and wiring closet.
To plan and create an acceptable operang environment for your device and prevent environmentally
caused equipment failures:
Keep the area around the chassis free from dust and conducve material, such as metal akes.