K-Commander Loss-in-Weight Programming
Rev: G Produced by the K-Tron Institute
LWF Page 04: Alarm Limits, Continued
Page 04
variable list
con't
Variable Name Edit? Description
Alarm Delay Setting ` Sets the time that a mass flow or
drive command alarm must be
pending before a hard alarm can
exist ( actuate the alarm system ).
Other alarms will bypass this delay
and immediately actuate the alarm
system.
Range of Values
5 to 240 seconds
Default value: 30 seconds
Start-up Delay Setting ` Sets the time, when the Run button
for a feeder is pressed, where the
massflow and drive command
alarms will not be permitted to
cause an alarm to occur.
Range of Values
0 to 240 seconds
Default value: 60 seconds