V2.01
25359_EDEBDA0279-2320-1_EN
12
Control and display panel
Harmonics monitoring: Activated by set limit
Limit THD: 8%
Stage power: Not set
Stage power monitored: Deactivated
Discharge time: 180 seconds
Password: No password
(9999, meaning all functions are accessible)
Language display: English
Contrast setting: 4
Brightness setting: 5
Dimmer brightness: 0
Low load limit: 15 mA
Low load delay: 60minutes
Temperature measurement: On
Relay 6/12 as stage or fan: Fan
Alarm relay as error message
or fan: Error message
Fan switch-on temperature: > 28 °C
Fan switch-o temperature: < 23 °C
System switch-o temperature: > 48°C
System switch-on temperature: < 43°C
Learning mode menu display: O
Key sounds: On
Error message dialog after reset:
No measuring voltage: Message and alarm relay
No stage power: Message and alarm relay
Facility too small: Message and alarm relay
THD too high: Message and alarm relay
Operating cycle limit exceeded: Message and alarm relay
No measuring current: Message and alarm relay
Low load operation: Message and alarm relay
Temperature switch-o: Message and alarm relay

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KBR multicomp F144-MS-1V1C1TI6RO-3 and is the answer not in the manual?

KBR multicomp F144-MS-1V1C1TI6RO-3 Specifications

General IconGeneral
BrandKBR
Modelmulticomp F144-MS-1V1C1TI6RO-3
CategoryController
LanguageEnglish

Related product manuals