1 x remote acknowledgement, 24 V, via volt-free contact
Process outputs
1 x volt-free signalling output (250 V, 1 A, changeover contact)
1 x signalling output (12.6 to 13.2 V), e.g. for connecting a horn, alarm
combination or alarm strobe light (12 V connection)
Rechargeable battery
Connection for rechargeable battery, for mains-independent power supply of:
Electronics
Sensors
Alarm equipment
Battery life/charging time
Battery life
Approx. 10 hours when supplying the integrated piezo buzzer 85 dB(A),
electronics, and sensors
Approx. 4 hours when supplying external alarm equipment (e.g. horn, alarm
combination, or alarm strobe light)
Charging time
Approx. 11 hours (if battery is fully discharged)
4.7 Fluids handled
WARNING
Pumping of impermissible fluids
Hazardous to persons and the environment!
Only discharge permissible fluids into the public sewer system.
Check the suitability of pump/system materials.
mini-Compacta, standard variant
According to DIN 1986-3 the following fluids can be discharged into sewer systems:
Water contaminated by domestic use, human and - as far as required and permitted -
animal faeces together with the necessary flushing water as well as stormwater in
case no other way of disposal is possible.
3)
Substances / water which must not be discharged into the sewer system are, amongst
others:
Solid matter, fibres, tar, sand, cement, ash, coarse paper, paper towels, cardboard,
debris, garbage, offal, grease, oil.
Waste water from installations situated above the flood level (EN 12 056-1).
Waste water containing hazardous substances (DIN 1986-100), e.g. greasy waste
water from large-scale catering kitchens.
For drainage of greasy water a grease separator to DIN 4040-1 must be fitted.
mini-Compacta, C variant
In addition to the fluids approved for the standard variant, this lifting unit is also
suitable for handling aggressive fluids:
Permissible
fluids
Impermissible
fluids
Additional permissible
fluids
3)
Other types of waste water, e.g. industrial waste water, must not be discharged into the local sewer system without prior
treatment.
4 Description