Actions Required during
Replace shaft seal and rotor, if required. ➀ ➁
Check flexible pipe connections for proper fit and wear, if any. ➀ ➁
Check expansion joints (if any) for wear. ➀ ➁
Check the shut-off, drain/vent and check valves for proper functioning and tightness. ➀ ➁
Check the collecting tank.
Clean tank from deposits, if any.
In case of major grease deposits in the tank as a result of greasy waste water from industrial
businesses, inform the customer that according to DIN 1986-100 a grease separator must be
installed (upstream of the lifting unit).
Check cover 160 for leakage.
➀ ➁
Check fuses.
Size, characteristics, three poles/interlocking device
➀ ➁
Replace the fuses after two years of operation (cartridges). ➀ ➁
Check the pump/motor for smooth operation. ➀ ➁
Check power consumption of motor(s). ➀ ➁
Test-run for several start/stop cycles. ➀ ➁
Check the alarm device to ensure that it functions properly. ➀ ➁
Replace the rechargeable battery after 5 years of operation. (⇨ Section 7.3.5 Page 40)
➁
Determine the spare parts requirements, if any. ➀ ➁
Advise and/or train operating staff. ➀ ➁
Provide new operating manual if necessary. ➀ ➁
8 Servicing/Maintenance
mini-Compacta
51 of 86