36
Installation and Connection
3.3 Connection of Power Circuit
3.3.1 Terminalstrip X1A
Terminal strip X1A / 230 V - class
suitable for
180...260 V AC / 1-phase (L1/N)
180...260 V AC / 3-phase (L1, L2, L3)
DC-Supply 250...370 V DC (++, --)
Terminal strip X1A / 400 V - Class
suitable for
305...500 V AC / 3-phase (L1, L2, L3)
DC-Supply 420...720 V DC (++, --)
Absolutely observe the connecting voltage of the KEB COMBIVERT. A 230V-unit
will be immediately destructed on a 400V-power supply.
Never exchange the mains and motor cables.
Some countries demand that the PE-terminal is directly connected to the terminal
box (not over the mounting plate).
W
V
U
PB
--
++
L3
N/L2
L1
T1
T2
W
V
U
PB
--
++
L3
L2
L1
T1
T2
++, PB Braking resistor
U, V, W Motor
T1, T2 Temperature sensor / switch (see chapter 3.3.6)