KeContact P20 Installation
Installation manual, Version: 1.41 / Article no.: 90064 35
© KEBA 2012-2013
SETTING THE AMPERAGE (DSW1) (*1)
Current
D1.6 D1.7 D1.8
Figure
10A
OFF OFF OFF
13A
ON OFF OFF
16A
OFF ON OFF
20A
ON ON OFF
25A
OFF OFF ON
32A
ON OFF ON
(*1) Preadjusted maximum current value for the EV charger (control pilot duty cycle).
STANDARD MODE + DHCP (NO ADDRESSING)
DSW2.1 to DSW2.4=OFF / DSW2.6=OFF
The charging procedure in STANDARD mode is
carried out automatically by the charging station
without higher-ranking control system.
The charging station attempts to obtain an IP
address via DHCP server, if needed.
This also corresponds to the basic settings for
charging stations without network connection.