16.4 [dP] Disable (pre-activated) first stage relay contact
Selecting [dP] shall disable the Preactivated (1
st
stage) relay output. The 1
st
Stage Contact
disabled and General Disablement indicators shall illuminate whilst the Preactivated relay is
disabled.
16.5 [dA] Disable (activated) second stage relay contact
Selecting [dA] shall disable the Activated (2
nd
stage) relay output) The 2
nd
Stage Contact disabled
and General Disablement indicators shall illuminate whilst the Activated relay is disabled.
16.6 [dc] Disable extract fan relay
Selecting [dc] shall disable the Extract fan output. The Extract Fan Disabled and General
Disablement indicators shall illuminate while the Extract Fan output is disabled.
16.7 [dt] Disable manual triggering device (manual release)
Selecting [dt] shall disable the Manual Release input. The Manual Release Disabled and General
Disablement indicators shall illuminate while the Manual Release input is disabled.
16.8 [dE] Disable extinguishant release
If the extinguishant release is disabled, the pre-release timer is never started and the
extinguishant output is never asserted.
Note: Extinguishant output faults are ignored while the extinguishant release is disabled.
16.9 [Ad] Activate delays
Selecting [Ad] shall make delays configured by access level 3 options C00 to C09 active.
16.10 [Ac] Operate extract fan output
Pressing the enter button with Ac selected will toggle the extract output on and off.