Product Manuals/Man-1088_Sigma XT_26 Page 36 of 40
C21* DISABLE FIRE BUZZER
C22* DISABLE FIRE OUTPUT
C23 DISABLE FAULT OUTPUT
C24 DISABLE EARTH FAULT MONITORING
C25 PULSE R0V OUTPUT
C26 REMOVE AUX 24V ON SYSTEM RESET
C27 INDICATE EXTING RELEASED WHEN EXTING OUTPUT
IS ACTIVE
C28 NO ACTIVATION DELAY UPON MANUAL RELEASE
C29 EXTINGUISHANT OUTPUT CAN BE RESET DURING
IMMINENT PHASE
C2A LOCAL FIRE RELAY OPERATES UPON RELEASED
SIGNAL
C2b* EXTINGUISHING OUPUT ON TILL RESET
C2C LOW PRESSURE SWITCH NORMALLY CLOSED
C2d DELAY MAINS FALI INDICATION BY 30 MINUTES
C31 ZONE 1 ALARM FROM DETECTOR DELAYED
C32 ZONE 2 ALARM FROM DETECTOR DELAYED
C33 ZONE 3 ALARM FROM DETECTOR DELAYED
C41 ZONE 1 ALARM FROM CALL POINT DELAYED
C42 ZONE 2 ALARM FROM CALL POINT DELAYED
C43 ZONE 3 ALARM FROM CALL POINT DELAYED
C61 ZONE 1 OPERATES THROUGH I.S. BARRIER
C62 ZONE 2 OPERATES THROUGH I.S. BARRIER
C63 ZONE 3 OPERATES THROUGH I.S. BARRIER
C71* ZONE 1 SHORT CIRCUIT INDICATES ALARM
C72* ZONE 2 SHORT CIRCUIT INDICATES ALARM
C73* ZONE 3 SHORT CIRCUIT INDICATES ALARM
C81* ZONE 1 NON-LATCHING
C82* ZONE 2 NON-LATCHING
C83* ZONE 3 NON-LATCHING
CA1 Z1 DEVICE ALARM MUST BE PRESENT FOR 30
SECONDS
CA2 Z2 DEVICE ALARM MUST BE PRESENT FOR 30
SECONDS
CA3 Z3 DEVICE ALARM MUST BE PRESENT FOR 30
SECONDS
E00 PANEL CAN BE RESET IMMEDIATELY DISCHARGE
OUTPUT HAS OPERATED
E01
TO
E29
PANEL CAN BE RESET 1 MINUTE TO 29 MINUTES
AFTER DISCHARGE OUTPUT HAS OPERATED
E30 PANEL CAN BE RESET 30 MINUTES AFTER
DISCHARGE OUTPUT HAS OPERATED
-00 NO EXTINGUISHANT DELAY
-05 5 SECONDS EXTINGUISHANT DELAY
-10
TO
-55
INCREMENT EXTINGUISHANT DELAY IN FIVE
SECOND STEPS
-60 60 SECONDS EXTINGUISHANT DELAY
060 EXTINGUISHANT DURATION TIME IN SECONDS
060
TO
295
INCREMENT EXTINGUISHANT DURATION IN FIVE
SECOND STEPS
300 EXTINGUISHANT DURATION TIME IN SECONDS
NOTE: Setting the option C15 marked with asterisks does not comply with EN12094-1