2-1September 2004
Argonite
®
Engineered Fire Suppression System
38-KFSARG-000
2-1 INTRODUCTION
Argonite
®
systems extinguish fires by the following methods:
2-1.1 Total Flooding
Release of Argonite into an enclosure (total flooding) means that an inert atmosphere is
created within the entire room volume.
2-1.2 Selector Valves/Distribution System
If more than one room or hazard in a building is to be protected, a common Argonite
cylinder bank may be used. The capacity of the cylinder bank must be calculated for
protection of the largest room/ hazard and/or adjoining rooms/hazards that may be
involved in a fire simultaneously. In most cases, Argonite selector valve systems reduce
the cost as compared to individual systems protecting the same hazards.
2-1.3 Modular System
In limited space areas where the authority having jurisdiction will allow for a modular system,
cylinders located singly or in multiple units within the room may be used. The total quantity
of stored agent, the number of nozzles etc., shall be that as required for a central bank
system. Cylinders shall be connected either electrically or pneumatically, allowing for
simultaneous discharge. Each individual unit shall be treated as a separate system.
CHAPTER 2
FIRE EXTINGUISHMENT METHODS