7-7
September 2004
Argonite
®
Engineered Fire Suppression System
38-KFSARG-000
Table 7-4. Total Flooding Quantities, Volume Requirements for ENVIRO-55 (US Standard, Mx [kg/
ft.
3
])
Temperature
(°F)
Typical Design Concentration (% by Volume)
From NFPA 2001
34 38 40 42 46 50 54
-20 0.02404 0.02765 0.02955 0.03151 0.03565 0.04010 0.04492
-10 0.02295 0.02642 0.02827 0.03013 0.03407 0.03829 0.04294
0 0.02199 0.02529 0.02706 0.02883 0.03259 0.03668 0.04109
10 0.02107 0.02422 0.02586 0.02759 0.03123 0.03513 0.03936
20 0.02019 0.02323 0.02479 0.02648 0.02991 0.03365 0.03770
30 0.01935 0.02228 0.02379 0.02538 0.02874 0.03232 0.03620
40 0.01858 0.02141 0.02284 0.02437 0.02758 0.03104 0.03476
50 0.01789 0.02058 0.02195 0.02343 0.02650 0.02981 0.03341
60 0.01722 0.01978 0.02111 0.02254 0.02550 0.02867 0.03212
70 0.01657 0.01904 0.02032 0.02171 0.02454 0.02761 0.03096
80 0.01595 0.01834 0.01957 0.02092 0.02366 0.02659 0.02979
90 0.01536 0.01770 0.01887 0.02015 0.02280 0.02564 0.02872
100 0.01482 0.01704 0.01821 0.01946 0.02198 0.02473 0.02771
110 0.01430 0.01645 0.01756 0.01874 0.02122 0.02385 0.02674
120 0.01383 0.01591 0.01696 0.01813 0.02049 0.02304 0.02585
130 0.01335 0.01536 0.01641 0.01750 0.01980 0.02227 0.02495