7-21 SIGNS AND LABELING
7-21.1 Storage Room
All doors to the system storage room shall be marked with a sign with the following
text in the local language:
Argonite Cylinder Storage Room: Before entering, ensure Oxygen content is
above 18%.
7-21.2 Argonite Cylinders
Each cylinder is labeled with an Argonite label. The purpose of the label is to provide
filling information, transport/safety information, inspection information and general
precautions to be taken during reinstallation of the cylinder.
7-21.3 Warning Alarms and Signs
Audible and visual alarm devices within, as well as outside the enclosure, shall be
provided with warning signs.
WARNING
LEAVE AREA IMMEDIATELY
WHEN ALARM SOUNDS
DO NOT RE-ENTER AREA
AFTER THE
SYSTEM IS DISCHARGED
UNLESS VENTILATED
THIS AREA PROTECTED BY
AN ARGONITE
FIRE SUPPRESSION SYSTEM
Figure 7-3. Exit Warning Sign, P/N 38-509859-001
WARNING
DO NOT ENTER AREA
WHEN ALARM IS SOUNDING
THIS AREA IS PROTECTED
BY AN ARGONITE
FIRE SUPPRESSION SYSTEM
AREA MUST BE VENTILATED PRIOR TO RE-ENTRY
Figure 7-4. Entrance Warning Sign, P/N 38-509860-001