Chapter 2: Front panel programming
116 P/N 3102351-EN • REV 005 • ISS 28DEC18
Description
Set auto signal silence to:
Off: Does not allow the panel to automatically silence the signals.
5 to 30 minutes: Allows the panel to automatically silence the signals after
the selected time period expires.
Set the timer duration. The range of possible values is 1 to 10 minutes.
The default value is 10 minutes.
Set the start time for daytime sensitivity.
Set the start time for nighttime sensitivity.
Set the date format to:
U.S.: MM/DD/YYYY
Canada: DD/MM/YYYY
Enter the desired banner text for line one and line two using the keypad.
Each line can have up to 20 characters. When you have finished, choose
Save. The LCD banner does not display when the panel is in any off-
normal state.
On: “Reset” temporarily turns off the resettable aux power output. This is
required when the output is used for powering four-wire smoke or four-
duct smoke detectors.
Off: “Reset” does not turn off the resettable aux power output. This is
required when the output is used to power remote annunciators.
Set event notification to:
Zone: When a device is a member of a zone, only the zone information is
sent to the LCD, LEDs, printer, and dialer. Note, device level reporting
configuration is not available.
Zone/device: Zone information is sent to the LCD and LEDs. Device
information is sent to the printer and dialer. Zone/dev
can be configured through custom programming.
Device: Only device information is reported, no zone information.
LED annunciator operation note: If you are using the optional LED
expanders, the zone LEDs are assigned to device addresses 1 to 32 on
loop 1. For example, zone 1 LEDs (red and yellow) are assigned to device
1 on loop 1. If the device is a dual element detector (single address), then
only the primary element is assigned to zone LED. All activations from the
secondary element are ignored by the zone LED.
Remote annunciator operation note: If you are using the optional remote
annunciators, when an event takes place on loop 1, the loop displays on
the annunciator LCD as loop 17 (not loop 1). The device number of the
device reporting the event is the correct device number. So, if an event
takes place on loop 1, the remote annunciators will display it as loop 17.
Loop 2 events will display on the annunciator LCD as loop 2 events. Loop
3 events will display on the annunciator LCD as loop 3 events. Loop 4
events will display on the annunciator LCD as loop 4 events.