When an audible alarm goes off, it is possible to acknowledge it pressing OK key on the transmitter.
3.5.2 Set the alarm in rising or falling edge
The alarm mode “Rising edge” or “Falling edge” is selected.
Go to the “Configuration” line then press OK.
Press OK on the “Channel” line and select the channel where the alarm will be active.
Press OK to validate.
Go to the “Threshold” line then press OK.
Use Up/Down/Left/Right arrows to enter a threshold then press OK.
Go to the “Hysteresis” line then press OK.
Use Up/Down/Left/Right arrows to enter the hysteresis value then press OK.
Go to the line “Threshold delay” then press OK.
Use Up/Down/Left/Right arrows to enter the value of threshold delay in second then press OK (this value is
between 0 and 600 s).
Go to the “Hysteresis threshold” then press OK.
Use Up/Down/Left/Right arrows to enter the value of the hysteresis delay in second then press OK (this value is
between 0 and 600 s).
Go to the “Sound alarm” line then press OK.
Select “YES” to activate the audible alarm or “NO” not to activate it then press OK.
3.5.3 Configure the alarm in monitoring mode
The alarm mode “Monitoring” is selected.
Go to the “Configuration” line then press OK.
Press OK on the “Channel” line and select the channel where the alarm will be active.
Go to the “Threshold 1” line then press OK.
Use Up/Down/Left/Right arrows to enter the threshold 1 then press OK.
Go to the “Threshold 2” line then press OK.
Use Up/Down/Left/Right arrows to enter the threshold 2 then press OK.
Go to the “Delay 1” line then press OK.
Use Up/Down/Left/Right arrows to enter the value of the delay 1 in second then press OK (this value is between 0
and 600 s).
Go to the “Delay 2” line then press OK.
Use Up/Down/Left/Right arrows to enter the value of the delay 2 in second then press OK (this value is between 0
and 600 s).
Go to the “Sound alarm” line then press OK.
Select “YES” to activate the audible alarm or “NO” not to activate it then press OK.
3.5.4 Configure the alarm on Transmitter state mode
16
Monitoring
The alarm goes off when the measurement is outside the low and
high thresholds.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kimo C310 and is the answer not in the manual?

Kimo C310 Specifications

General IconGeneral
Measured parametersCO, Temperature
CO measurement range0 to 500 ppm
CO resolution1 ppm
Temperature accuracy±0.5 °C
Temperature resolution0.1 °C
ProtectionIP65
Operating Humidity0 to 95% RH (non-condensing)
Response Time< 30 seconds
Power supply24 V AC/DC
Output4-20 mA