4. Description of function and Modbus connections
4.1. Device
Modbus Register type Description Possibilities
1000 - Serial number of the
transmitter
1010 - Firmware version
1400 - Keypad locking 0 : deactivated
1 : activated
1410 U16 Security code
1500 U8 Modbus slave number From 1 to 255
1510 Enumeration Modbus speed
communication
2400 / 4800 / 9600/ 19200 / 38400 /
115200 bds
1700 - Activation of the high
resolution in pressure
option
1 : activated / 0 : deactivated
1710 - Activation of the
Modbus option
1 : activated / 0 : deactivated
1900 - Back to factory
configuration
4.2. Channels
Modbus Register type Description Possibilities
2000 Enumeration Unit selection of the
channel 1
Probe
Board
Deactivated
2100 Enumeration Unit selection of the
channel 2
Probe
Board
Deactivated
2200 Enumeration Unit selection of the
channel 3
Probe
Board
Deactivated
2300 Enumeration Unit selection of the
channel 4
Probe
Board
Deactivated
2010 Enumeration Activation/deactivation
of the channel 1
According to probe and board
2110 Enumeration Activation/deactivation
of the channel 2
According to probe and board
2210 Enumeration Activation/deactivation
of the channel 3
According to probe and board
2310 Enumeration Activation/deactivation
of the channel 4
According to probe and board
24

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kimo C310 and is the answer not in the manual?

Kimo C310 Specifications

General IconGeneral
Measured parametersCO, Temperature
CO measurement range0 to 500 ppm
CO resolution1 ppm
Temperature accuracy±0.5 °C
Temperature resolution0.1 °C
ProtectionIP65
Operating Humidity0 to 95% RH (non-condensing)
Response Time< 30 seconds
Power supply24 V AC/DC
Output4-20 mA