3.2.3.1 Operation Modes and Inputs of the High-speed Counters
Input signals of high-speed counter include: clock (input impulse), direction, start and reset.
In different operation modes input signals is different. Please see below:
HSC 0
Mod
e
Description
I0.1
I0.0
I0.5
0
Single-phase up/down counter
with internal direction control:
SM37.3
Clock
1
Reset
2
Reset
Start
3
Single-phase up/down counter
with external direction control
Clock
Direction
4
Reset
Direction
6
Two-phase counter with up/down
clock inputs
Clock
Down
Clock Up
9
A/B phase quadrature counter
Clock A
Clock B
HSC 1
Mode
Description
I0.4
I0.6
I0.3
I0.2
0
Single-phase up/down counter
with internal direction control:
SM47.3
Clock
1
Reset
2
Reset
Start
3
Single-phase up/down counter
with external direction control
Clock
Direction
4
Reset
Direction
6
Two-phase counter
with up/down clock inputs
Clock
Down
Clock Up
7
Reset
9
A/B phase quadrature counter
Clock A
Clock B
10
Reset
HSC 2
Mode
Description
I0.4
I0.5
0
Single-phase up/down counter
with internal direction control:SM57.3
Clock
9
A/B phase quadrature counter
Clock A
Clock B

Related product manuals