TP-5606 6/02 Specifications 1-1
Section 1. Specifications
Introduction
This manual provides troubleshooting and repair
instructions for the 15/20CCO, 15/20CCFO,
15/20CCOZ, and 15/20CCFOZ model generator sets,
controllers, and accessories.
Refer to the engine service manual for generator set
engine service information.
x:in:001:001
This manual may be used for models not listed on the
front cover.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
The equipment service requirements are very important
to safe and efficient operation. Inspect the parts often
and perform required service at the prescribed intervals.
Obtain service from an authorized service distributor/
dealer to keep equipment in top condition.
x:in:001:002:a
General Specifications
15 kW (60 Hz) Model 20 kW (60 Hz) Model
Dimensions L x W x H in. (mm):
Remote Radiator (Single Phase) 39.57 x 20.89 x 25.61 39.57 x 20.89 x 27.25................... .....
(1005 x 531 x 650) (1005 x 531 x 692)
Remote Radiator (Single Phase) Airbag Mounted 39.57 x 22.00 x 25.61 39.57 x 22.00 x 27.25..... .....
(1005 x 559 x 650) (1005 x 559 x 692)
In-line Radiator (Single Phase) 45.02 x 20.99 x 28.00 45.02 x 20.99 x 28.00..................... .....
(1144 x 533 x 711) (1144 x 533 x 711)
In-line Radiator (Three Phase) 46.62 x 20.99 x 28.00 46.62 x 20.99 x 28.00..................... .....
(1184 x 533 x 711) (1184 x 533 x 711)
Weight—dry, lbs. (kg):
Remote Radiator (Single Phase) 684 (310) 695 (315)........................ ................
Remote Radiator (Single Phase) Airbag Mounted 684 (310) 695 (315).......... ................
In-line Radiator (Single Phase) 719 (326) 730 (331).......................... ................
In-line Radiator (Three Phase) 719 (326) 730 (331).......................... ................
Air Requirements CFM (M
3
/min):
Combustion. 70 (2) 70 (2)........................................... ...................
Cooling 1930 (55) 1930 (55).............................................. ................
Fuel Inlet Size in. (mm) 1/4-18 N.P.S.F 1/4-18 N.P.S.F.................................. ...........
Fuel Return Size in. (mm) 1/4-18 N.P.S.F 1/4-18 N.P.S.F................................ ...........
Fuel Consumption gph (Lph):
Load 25% 50% 75% 100%
15 kW 0.6 (2.3) 0.8 (3.0) 1.1 (4.2) 1.4 (5.3)
20 kW 0.9 (3.4) 1.2 (4.5) 1.5 (5.7) 1.9 (7.2)
DERATION: All units are rated 1.0 power factor. The kilowatts of the generator set will decrease 3.5% for each 1,000
feet (305 meters) above 500 feet (152 meters) above sea level and 1% for each 10_F (5.5_C) above 85_F (30_C).