TP-6694 9/20 39
Description
Controller
Display
Message
Alarm
Horn
Fault
Lamp
Warning
Shutdown
Write
Access
Display
SiteTech
GenSet
Mode
Always
Running
Stopped
Range
Setting
Default
Selection
Time
Delay
Range
(sec.)
Default
Time
Delay
(sec.)
Charger Depleted Battery
Voltage Target
S
412
(12 V)
1824
(24 V)
10
(12 V)
20
(24 V)
Charger Equalize Stage
Duration (Min)
Note:
Equalize is only available with
FLA/VRLA topology selected.
S
A
60480
Charger Manual Equalize
Cycle Activation
Note:
Equalize is only available with
FLA/VRLA topology selected.
S
A
Active
Inactive
Inactive
Charger Maximum Absorption
Time Threshold (Min.)
S
A
60360
60600
(NiCad
only)
240
Charger Maximum Bulk Time
Threshold (Min)
S
A
6600
480
Charger Refresh Charge
Cycle Time (Hr)
S
A
0,
23672
335
Charger Return To Bulk State
Voltage Threshold (V)
S
A
1013
(12 V)**
2026
(24 V)**
12.8
(12 V)
25.6
(24 V)
Charger Starter Battery
Topology
Note:
Verify that the battery topology
is set correctly for the battery
type that is used.
Incorrect charger output
system voltage may cause
irreversible damage to the
battery and abnormal out
gassing.
S
A
Default
FLA/
VRLA
AGM
Gel
NiCad
Default
Charger System Battery
Voltage
Note:
Verify that the system
voltage is set correctly for
the battery type that is used.
Incorrect charger output
system voltage may cause
irreversible damage to the
battery and abnormal out
gassing.
S
A
System
12 VDC
System
24 VDC
12 VDC
Charger Temperature
Compensation Enable
S
A
Active
Inactive
Inactive
Charger Temperature
Compensation Slope (mV/ C)
S
A
-400
(12 V)
-800
(24 V)
-30
(12 V)
- 60
(24 V)
* Function requires optional input sensors or is engine ECM dependent on some generator set models.
ECM inputs are engine-manufacturer dependent.
Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
ST- Short Term, LT- Long Term

Table of Contents

Other manuals for Kohler Decision-Maker 3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Maker 3000 and is the answer not in the manual?

Kohler Decision-Maker 3000 Specifications

General IconGeneral
BrandKohler
ModelDecision-Maker 3000
CategoryController
LanguageEnglish

Related product manuals