Controller
Display
Message
Fault
Lamp
Warning
Shutdown
Write
Access
Display
SiteTech
GenSet
Mode
Always
Running
Stopped
Default
Time
Delay
(sec.)
Charger Voltage Absorption (V)
13–15
(12 V)**
26–30
(24 V)**
13–15
(12 V)**
26–30
(24 V)**
Charger Voltage Equalize (V)
Note:
Equalize is only available with
FLA/VRLA topology selected.
14–16
(12 V)
28–32
(24 V)
Charger Voltage Float (V)
13–14
(12 V)**
26–28
(24 V)**
Current transformer ratio ‡
Engine (cyclic) crank pause
Engine no. of (cyclic) crank
cycles
Equalize Current Limit (A)
Note:
Equalize is only available with
FLA/VRLA topology selected.
Forced Charge Cycle Reset
Voltage regulator stability
adjust
Voltage regulator, volts per
Hertz slope
Voltage regulator, volts per
Hertz cut in frequency
* Function requires optional input sensors or is engine ECM dependent on some generator set models.
† ECM inputs are engine-manufacturer dependent.
‡ Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
ST- Short Term, LT- Long Term