26.03.1996 • KHH SEENXL13A
•For Authorized KCI Service Agents Only•
KCI Hoists Corporation reserves the right to alter or amend the above information without notice
Page 25
XL
Service Manual
CU1
KCI KONECRANES GROUP
KCI HOISTS CORPORATION
1-400
1-4001-400
1-400 Message log: 10 last Err-mes
Message log: 10 last Err-mesMessage log: 10 last Err-mes
Message log: 10 last Err-messages
sagessages
sages (> P2.13)
Displays the last 10 Err-messages and corresponding STARTS values for
those. Also the following messages can be displayed:
- E 30 (the message log has been initialized)
- E 31 (CU1 has been started i.e. power switched on)
- E 32 (hoisting prevented because of overload; LOAD > 110%)
- E 33 (hoisting prevented because of underload; LOAD < -10/20%)
- E 34 (hoisting prevented because of overheating; TEMP)
- E 35 (hoisting prevented because of brake alarm; BRAKE)
- E 36 (lowering motion of the motor has been used when brake
alarm was on)
- E 37 (hoisting prevented, reason unknown)
1-401
1-4011-401
1-401 Err-message log: number of Err-message situations
Err-message log: number of Err-message situationsErr-message log: number of Err-message situations
Err-message log: number of Err-message situations (> P2.13)
Displays the total number of above mentioned Err-messages.
1-630
1-6301-630
1-630 Beginning of the p
Beginning of the pBeginning of the p
Beginning of the programming and controlling mode
rogramming and controlling moderogramming and controlling mode
rogramming and controlling mode
Shifts the CU1 into the programming and controlling mode.
2-611
2-6112-611
2-611 Setup mode, procedure 1
Setup mode, procedure 1Setup mode, procedure 1
Setup mode, procedure 1
Load sensor calibrating with 0 and 100 % loads.
2-622
2-6222-622
2-622 Setup mode, procedure 2
Setup mode, procedure 2Setup mode, procedure 2
Setup mode, procedure 2
Load sensor calibrating with 0 and 50-99 % loads.
2-601
2-6012-601
2-601 Setup mode, procedure 3
Setup mode, procedure 3Setup mode, procedure 3
Setup mode, procedure 3 (> P2.12)
Load sensor calibrating with 0 and 110 % loads.
2-645
2-6452-645
2-645 Setup mode, procedure 4
Setup mode, procedure 4Setup mode, procedure 4
Setup mode, procedure 4 (> P2.12)
Load sensor calibrating with 0 and 125 % loads.
2-224
2-2242-224
2-224 Checking of supervisory values
Checking of supervisory valuesChecking of supervisory values
Checking of supervisory values (> P2.12)
Checks SWP, Run Time, Starts and Overload values (i.e. a memory test).
2-410
2-4102-410
2-410 Initalization off Message log
Initalization off Message logInitalization off Message log
Initalization off Message log
Initilizates the Message logs 1-400 and 1-401
2-865
2-8652-865
2-865 Option 1; Bypassing of low voltage detector for 0,5 sec
Option 1; Bypassing of low voltage detector for 0,5 secOption 1; Bypassing of low voltage detector for 0,5 sec
Option 1; Bypassing of low voltage detector for 0,5 sec (> P2.12)
Bypasses the low voltage detector for 0,5 seconds during starting (and while
driving >P2.13) the hoisting motor (see Appendix 6).
2-764
2-7642-764
2-764 Option 2; Changing direction
Option 2; Changing direction Option 2; Changing direction
Option 2; Changing direction (> P2.12)
Changes the operation of CU1's internal check routine in order to avoid
Err_10 situation when changing direction from downwards to upwards (see
Appendix 6). This option is normally selected always as factory default
>P2.13).