EasyManua.ls Logo

Kostal ENECTOR - Page 68

Kostal ENECTOR
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning/configuration
1 12345678910111213141516
© 2022 KOSTAL Solar Electric GmbH68
BankDIP switchCharging current
per phase (A)
Charging power (kW)
321Connection
1-phase3-phase
ONONOFF61.44.1
Setting the house connection current
The maximum current per phase of the house connection must be set so that it is not over-
loaded when charging an electric vehicle (blackout protection).
NOTE
Nature and source of hazard
The maximum current which can be set per phase of the house connection depends on
the fuse protection at the grid connection point (e.g. 63 A) and house connection box
(e.g. 50 A downstream of grid demand meter). The lowest fuse protection (in this ex-
ample 50 A) must be set here.
With a KOSTAL Smart Energy Meter and activated convenience functions, this setting for
overload protection is automatically transferred.
Configure the setting as desired.
Bank 2
Bank 1
12
45
3
678
ON
1245 36
78
ON
ON
OFF
Bank 2
1245 3678
ON
876
63 A
50 A
40 A
35 A
32 A
25 A
20 A
16 A
Configurable functions: