Application > Examples of application
1.1.8 IC 40, continuous control with defined ignition
position
The central control system starts the pre-purge. Input DI 2
is actuated via the air valve output of the BCU and moves
the butterfly valve BVA to the pre-purge position.
In the event of a temperature demand, the burner control
unit BCU actuates input DI 1 via the valve output V1 and
moves the butterfly valve to the ignition position.
(Precondition: the IC 40 must have reached the ignition
position on the instant of ignition.) The burner starts.
The BCU actuates DI 2 via the air valve output. This enables
the analogue input AI on the actuator IC 40. Depending
on the capacity demand of the temperature controller,
the butterfly valve BVA moves steplessly to the position
between the low-fire rate and the high-fire rate as
specified by the analogue input AI (see Operating mode
27, 2-step operation with two digital inputs and variable
adjustment angle).
Ignition position/low-fire rate
Any position between ignition