IC 40 function > Parameters
4 .7 .1 Parameter sets
Parameter set Operating mode Function
P68001 6 3-step operation with one or two digital inputs, running time: 6 s
P68010 10 3-point step operation with running time fractions, running time: 51 s
P68011 10 3-point step operation with running time fractions, running time: 30 s
P68012 5 3-point step operation, running time: 15 s
P68013 5 3-point step operation, running time: 7.5 s
P68014 5 3-point step operation, running time: 4.5 s
P68015 3 2-step operation with one or two digital inputs, running time: 51 s
P68016 3 2-step operation with one or two digital inputs, running time: 30 s
P68017 1 2-point operation, running time: 15 s
P68018 1 2-point operation, running time: 7.5 s
P68019 1 2-point operation, running time: 4.5 s
P68020 10 3-point step operation with running time fractions, running time: 15 s
P68021 2 2-point operation with flame proving period, running time: 4.5 s
P68022 4 2-step operation with two digital inputs, running time: 5 s
P68023 7 2-point operation with switchover of the adjustment angle for the “open”
position, running time: 4.5 s
P68024 8 2-point operation with input-dependent adjustment angle for the “open”
position, running time: 4.5 s