IC 40 function > Standard operating modes 1 – 12 > 3-point step
operation with running time fractions
The opening time results from the two successive running
times t1 and t2.
The closing time results accordingly from running times t3
and t4. “Middle” position is used as an interpolation point.
This can be defined individually.
Owing to the two successive running times, the opening
characteristic of the butterfly valve can be changed. For
example, the characteristic of the air circuit can be
adapted to that of the gas circuit.
Running times up to 51 s (2 x 25.5 s) are possible in this op-
erating mode.
Possible parameter sets for this operating mode: P 68010, P
68011 and P 68020, see page 54 (Parameter sets). 37