IC 40 function > Analogue operating modes 21 – 27
> 2-point operation with switchover of the running times
t4
The “high” position can be selected correspondingly lower
in order to obtain longer running times (> 25.5 s).The “high”
position does not limit the adjustment angle for the “open”
position but only defines the speeds.
Consequently, the “high” position may also be lower than
the “analogue” position. The magnitude of the current
signal is crucial as regards the “analogue” position.
Possible parameter set for this operating mode: P 68029,
see page 54 (Parameter sets). 46