KSB Delta Macro
1983.843/04-EN
Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re-start
required
1-1-3-2 Number of base load pumps 1 … (number of pumps - number of
peak-load pumps) if pump groups =
base-load and peak-load pump control
1 … (number of pumps - number of
jockey pumps) if pump groups = jockey-
pump control
Number of pumps Everybody Nobody Y
1-1-3-3 Number of peak load pumps 0 … (number of pumps - number of
base load pumps)
0 Everybody Service Y
1-1-4 Maximum system load - - Everybody Nobody -
1-1-4-1 Maximum number of pumps 0 … number of all pumps Number of all
pumps
Everybody Service -
1-1-5 Manual-0-automatic mode - - - - -
1-1-5-1 Manual-0-automatic mode of
pumps
Internal via display Internal via display Everybody Service -
External switches
1-1-6 Fire alarm - - - - -
1-1-6-1 Fire alarm mode Disabled Disabled Everybody Service -
Enabled
1-1-7 External On/Off - - - - -
1-1-7-1 External On/Off mode Disabled Disabled Everybody Service -
Enabled
1-1-8 Membrane rupture detection - - - - -
1-1-8-1 Membrane rupture detection Disabled Disabled Everybody Service -
Enabled
1-1-8-2 Digital input - - Everybody Nobody -
1-1-8-3 Source Water detection integrated Water-detection
on-board
Everybody Service -
Membrane rupture detection by
external device
1-1-8-4 Delay time membrane rupture
detection
0 … 99s 10s Everybody Service -
1-1-8-5 Delay time reset 0 … 99s 2s Everybody Service -