KSB Delta Macro
1983.843/04-EN
10.2.2 Settings
10.2.2.1 Pressure settings
Table29: Pressure settings parameters
Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re-start
required
2 Settings - - Everybody Nobody -
2-1 Pressure - - - - -
2-1-1 Setpoint 0 … 99bar 2bar Everybody Display/Customer -
2-1-2 Bandwidth 0 … 99bar 0.05 bar Everybody Customer -
2-1-3 Alternative setpoint 0 … 99bar 2.5 bar Everybody Customer -
2-1-4 Alternative setpoint selection Disabled Disabled Everybody Customer -
Time enabled
Digital input enabled
2-1-5 Alternative set-point start time
(hours)
0…24h 0 Everybody Customer -
2-1-6 Alternative set-point start time
(minutes)
0 … 60min 0 Everybody Customer -
2-1-7 Alternative set-point stop time
(hours)
0…24h 0 Everybody Customer -
2-1-8 Alternative set-point stop time
(minutes)
0 … 60min 0 Everybody Customer -
2-1-9 Additional setpoint increase 0 … 1bar 0.3bar Everybody Customer -
2-1-10 Minimum set-point 0 … 99bar 0bar Everybody Service -
2-1-11 Maximum set-point 0 … 99bar 99bar Everybody Service -
10.2.2.2 Pump operating mode
Table30: Pump operating mode parameters
Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re-start
required
2-2 Pumps - - Everybody Nobody -
2-2-1 Pump operating mode - - Everybody Nobody -
2-2-1-1 Pump 1 Automatic Manual-Off Everybody Display/Customer -
Manual-Off