EasyManua.ls Logo

KSB Delta Macro F - Messages for Additional Devices

KSB Delta Macro F
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Related Documents
82 of 92
KSB Delta Macro
1983.843/04-EN
ID
message
Parameter Description Status Reset mode
(factory
setting)
551 2-9-10-2 Fault frequency inverter pump 5 Alert Auto
552 2-9-10-3 Communication error frequency inverter pump 5 Alert Auto
553 2-9-10-4 Incorrect check sum frequency inverter pump 5 Alert Auto
554 2-9-10-5 Internal fault frequency inverter pump 5 Alert Auto
555 2-9-10-6 Mains fault frequency inverter pump 5 Alert Manual
556 2-9-10-7 Phase failure frequency inverter pump 5 Alert Manual
557 2-9-10-8 Overvoltage frequency inverter pump 5 Alert Auto
558 2-9-10-9 Undervoltage frequency inverter pump 5 Alert Auto
559 2-9-10-10 Overload frequency inverter pump 5 Alert Manual
560 2-9-10-11 Brake resistor frequency inverter pump 5 Alert Manual
561 2-9-10-12 Temperature fault frequency inverter pump 5 Alert Manual
562 2-9-10-13 AMA fault frequency inverter pump 5 Alert Manual
563 2-9-10-14 Short circuit frequency inverter pump 5 Alert Manual
564 2-9-10-15 Safety stop frequency inverter pump 5 Alert Manual
565 2-9-10-16 Configuration invalid frequency inverter pump 5 Alert Manual
600 2-9-11-1 Failure motor-circuit breaker pump 6 Warning Manual
601 2-9-11-2 Manual ON pump 6 Warning Auto
602 2-9-11-3 Manual OFF pump 6 Warning Auto
603 2-9-11-4 Excessive temperature motor pump 6 Alert Manual
650 2-9-12-1 Fault motor circuit breaker frequency inverter pump 6 Warning Manual
651 2-9-12-2 Fault frequency inverter pump 6 Alert Auto
652 2-9-12-3 Communication error frequency inverter pump 6 Alert Auto
653 2-9-12-4 Incorrect check sum frequency inverter pump6 Alert Auto
654 2-9-12-5 Internal fault frequency inverter pump 6 Alert Auto
655 2-9-12-6 Mains fault frequency inverter pump 6 Alert Manual
656 2-9-12-7 Phase failure frequency inverter pump 6 Alert Manual
657 2-9-12-8 Overvoltage frequency inverter pump 6 Alert Auto
658 2-9-12-9 Undervoltage frequency inverter pump 6 Alert Auto
659 2-9-12-10 Overload frequency inverter pump 6 Alert Manual
660 2-9-12-11 Brake resistor frequency inverter pump 6 Alert Manual
661 2-9-12-12 Temperature fault frequency inverter pump 6 Alert Manual
662 2-9-12-13 AMA fault frequency inverter pump 6 Alert Manual
663 2-9-12-14 Short circuit frequency inverter pump 6 Alert Manual
664 2-9-12-15 Safety stop frequency inverter pump 6 Alert Manual
665 2-9-12-16 Configuration invalid frequency inverter pump 6 Alert Manual
10.3.2 Messages for additional devices
Table39: Messages for additional devices
ID
message
Parameter Description Status Reset mode
(factory
setting)
700 2-9-13-1 Suction-side pressure too low Alert Manual
701 2-9-13-2 Suction-side pressure too high Alert Manual
702 2-9-13-3 Fault pressure sensor suction side Alert Manual
703 2-9-13-3 Broken wire pressure sensor suction side Alert Manual
704 2-9-13-4 Short circuit pressure sensor suction side Alert Manual
720 2-9-14-1 Discharge-side pressure too low Alert Manual
721 2-9-14-2 Discharge-side pressure too high Alert Manual

Table of Contents