KStar E8KT - 4.3 Configuration Menus Overview

KStar E8KT
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GRID
POWER
0…100%
100%
INV
VOLT
MAX
VOLT
(S1)
set upper
limit voltage
280Vac
set
protection
time
1000ms
VOLT
(S2)
set upper
limit voltage
285Vac
set
protection
time
400ms
INV
VOLT
MIN
VOLT
(S1)
set lower
limit voltage
150Vac
set
protection
time
1000ms
VOLT
(S2)
set lower
limit voltage
120Vac
set
protection
time
400ms
INV
FREQ
MAX
FREQ
(S1)
set upper
limit
frequency
55Hz
set
protection
time
500ms
FREQ
(S2)
set upper
limit
frequency
55Hz
set
protection
time
500ms
INV
FREQ
MIN
FREQ
(S1)
set lower
limit
frequency
45Hz
53
54
set
protection
time
500ms
FREQ
(S2)
set lower
limit
frequency
45Hz
set
protection
time
500ms
GRID U
MAX
Set max Grid voltage 280Vac
GRID U
MIN
Set min Grid voltage 130Vac
GRID F
MAX
Set max Grid frequency 55Hz
GRID F
MIN
Set min Grid frequency 45Hz
OVER
VOLT
Enable
Disable
Disable
Enable
VOLT
270V
UNDER
VOLT
Enable
Disable
Disable
Enable
User Manual User Manual
Limit or increase the power
exported from the system to
the grid.
These settings should not be
altered. They are set
automatically according to the
country selected within Grid
Setting.If the inverter sees
that these values have been
reached, or exceeded, then
the inverter will stop
generating.
set voltageIf
enabled,Once
the AC output
voltage
exceeds this
set value, the
output power
will start to
decrease.
Menu
Level 1
Menu
Level 2
Menu
Level 3
Menu
Level 4
Menu
Level 5
Menu
Level 6
Default
Selection
Comment
Menu
Level 1
Menu
Level 2
Menu
Level 3
Menu
Level 4
Menu
Level 5
Menu
Level 6
Default
Selection
Comment