EasyManua.ls Logo

KYORITSU 6050 - Page 15

KYORITSU 6050
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
(andtheprospectivefaultcurrenthighenough)toallowautomatic
disconnectionoftheelectricalsupplybythecircuitprotectiondevicewithina
prescribedtimeinterval.
Everycircuitmustbetestedtoensurethattheearthfaultloopimpedance
valuedoesnotexceedthatspecified or appropriate for theover-current
protectivedeviceinstalledinthecircuit.
ForaTTsystemtheearthfaultloopimpedanceisthesumofthefollowing
impedances;
Impedanceofthepowertransformersecondarywinding.
Impedanceofthephaseconductorresistancefromthepowertransformer
tothelocationofthefault.
Theimpedanceoftheprotectiveconductorfromthefaultlocationtothe
localearthsystem.
Resistanceofthelocalearthsystem(R).
Resistanceofthepowertransformerearthsystem(Ro).
ForTNsystemstheearthfaultloopimpedanceisthesumofthefollowing
impedances.
Impedanceofthepowertransformersecondarywinding.
Impedanceofthephaseconductorfromthepower transformer tothe
locationofthefault.
Impedanceoftheprotectiveconductorfromthefaultlocationtothepower
transformer.
Fig.9

Related product manuals