EasyManua.ls Logo

KYORITSU 6050 - Page 19

KYORITSU 6050
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
PracticalexampleofverificationoftheprotectionisaTTsystem
accordingtotheinternationalStandardIEC60364.
Fig.12
ThemaximumvalueofZsforthisexampleis2.1Ω(16ampgGfuse,0.4
seconds).The loop tester reads 1.14Ωand consequently the condition
Zs
<
Uo/laismet.
5.1.2PrinciplesoftheMeasurementofLineImpedanceand
ProspectiveShortCircuitCurrent
Lineimpedanceistheimpedance,whichismeasuredbetweenPhase-
terminalLandNeutral-terminal N of single-phasesystem,orbetween
twophasesofthree-phasesystem.Measurementprincipalusedinthis
instrumentisthesameasitforFaultloopimpedancemeasurement,but
measurementisperformedbetweenTerminalLandN,orbetweentwo
phases.
Breakingcurrentcapacityof installed over-current protectiondevices
shouldbehigherthanProspectiveShort-Circuitcurrent,otherwiseitis
necessarytochangetheratedcurrentofinvolvedover-current
protectiondevice.

Related product manuals