3 Operating instructions
3.1 Application
These operating instruction apply to the F 200 K compact flame detector.
The devices comply with the following standards and rules:
DIN EN 230
DIN EN 298
DIN VDE 0116
97/23/EG (directive on pressurised equipment)
90/396/EWG (directive on gas equipment)
DIN EN 60730, part 1 and IEC 801, part 5 (leakage paths and sparking-distance in air
as well as interference susceptibility)
Product identification no.: CE- 0085 BO 0005
3.2 Purpose intended
In single-burner and multiple-burner furnaces, the flame detector performs a high-
safety monitoring of the burner flames. When the flame goes out, the safe control
state “Flamme out“ is reached.
The flame detector is mainly used in large-scale power plants, thermal power stations
and chemical plants as well as for monitoring furnaces which are operated from
- OIL
- GAS
- BIO-MASS
- DUST COAL
- CHEMICALS AND OTHER WASTE PRODUCTS.
3.3 Design
The compact-type flame detector is composed of a cylindrical casing comprising a
light incidence aperture that is in line with the axis a processing status indicator on its
rear side as well as operational controls, which can be accessed there when removing
the cover.
When closed the flame detector complies with the requirements of IP 67 protection
degree.
The detector is installed at the burner by optionally using the FS 19, FV 19, FS 20, FV
20 adjustable holding devices or with an air-cooled housing of the FS 50 or FS 51
types.
The detector consists of the following functional units:
- Sensor unit providing for digitalisation of the flame signal
- digital frequency evaluation
- Self-monitoring
- Switching amplifier
The device is connected through an integrated standard plug and using the a connec-
tion cable required for this (8 pins, static screen,
cable type LiYCY 8x1x0,5 mm²) with coupler.