- 11 -
Vibration fatigue limit
according to EN 298, section. 6.5.2.2.2 2 g
function tested 5 g
Protection type IP 67; in closed state
Mass 0.6 kg
Storage conditions (in original packing)
Storage location closed premises
Air temperature - 40 ... +70 °C
Air humidity max. 80% at 35 °C
Transport conditions (in original packing)
Type of transport in closed holds
Air temperature - 40 ... + 70 °C
Temperature - humidity - coupling max. 80% at 35 °C
Wear and tear parts
n o n e
5 Selection criteria
Type Spectral range Application - Fuel type
F 200 K1 UV-1 260 ... 400 nm Oil, gas
F 200 K2 UV-1 (Ex)
F 200 K1 UV-2 210 ... 280 nm Oil, gas (special gasses such as
F 200 K2 UV-2 (Ex) refinery and blast furnace gases)
F 200 K1 IR 2 850 … 1200 nm Monitoring of combustion chambers
F 200 K2 IR-2 (Ex) and burn edges (coal, wood)
F 200 K1 IR-1 1200 ... 2800 nm Oil, gas, wood, coal, furnaces with
F 200 K2 IR-1 (Ex) heavy flue gas recirculation, waste
gasses with yellowish colour with-
out UV radiation and/or screening
of the UV portions by vapour, dust
etc.

Table of Contents