46
11 Appendix
11 Appendix
11.1 Technical Data
11.1.1 Flame Monitor F152
Fig. 11-1 Dimensions F152
1
The product must not be transported, stored or operated outside the specified range. If it is, any guarantees with regard to safety-
related functions lose their validity.
Input parameters
Axillary energy
Supply voltage
1
230 VAC +10 % -15 %
115 VAC +10 % -15 %, on site
120 VAC +10 % -20 %, UL Recognized version
Mains frequency
1
50/60 Hz
Power consumption 5 VA
Device fuse (soldered) 0.1 A (230 V); 0,2 A (115/120 V); delay fuse