66
DMX
3
9. Features of the main electrical accessories
Motor operator
Technical features
Rated operating voltage Vn (Va.c.): 24V-48V-110V÷130V-220V÷250V-415V÷440V
(Vd.c.): 24V-48V-110V÷130V-220V÷250V
Voltage range (% Vn): 85÷110
Maximum power consumption (W/VA): 240/240
Maximum peak current for about 80ms: 2÷3xIn
Charging time (s): 5
Operating frequency (n°/min): 2
Closing coil
Technical features
Rated operating voltage Vn (Va.c.): 24V-48V-110V÷130V-220V÷250V -415V÷440V
(Vd.c.): 24V-48V-110V÷130V-220V÷250V
Voltage range (% Vn): 85÷110
Pick-up consumption (W/VA): 400/400
Pick-up time (ms): 300
Hold consumption (W/VA): 50/50
Closing time (ms): 50
Insulation voltage (kV): 2,5
Shunt trip
Technical features
Rated operating voltage Vn (Va.c.): 24V-48V-110V÷130V-220V÷250V - 415V÷440V
(Vd.c.): 24V-48V-110V÷130V-220V÷250V
Voltage range (% Vn): 70÷110
Pick-up consumption (W/VA): 400/400
Pick-up time (ms): 300
Hold consumption (W/VA): 50/50
Opening time (ms): 50
Insulation voltage (kV): 2,5
Undervoltage release
Technical features
Rated operating voltage Vn (Va.c.): 24V-48V-110V÷130V-220V÷250V -415V÷440V
(Vd.c.): 24V-48V-110V÷130V-220V÷250V
Voltage range (% Vn): 85÷110
Pick-up consumption (W/VA): 400/400
Pick-up time (ms): 300
Hold consumption (W/VA): 50/50
Opening time (ms): 60
Insulation voltage (kV): 2,5