Parameter Descriptions
1. S-Bus Address
Options are 1 through 31. Select address and
press the set button to save the setting and
return to the technician setting screen.
NOTE: S-Bus address should be the same as the
address being used by either the NTC or
unit controller which you wish to control
with the CS8500.
2. Operation with Smart Hub
directly with a Prodigy Unit Controller via the
In addition, when set to ON, this function will
allow the CS8500 to operate in a BACnet
network with an M3 Unit Controller or operate
with an iCON Hub / NTC.
3. Local Scheduling Function
This feature provides the ability to setup a local
schedule. When set to ON, several options are
the scheduling function can be turned on from
the home screen by selecting heat/cool on the
home screen and select mode schedule.
If the ComfortSense 8500 is in stand-alone
mode, local scheduling can be used. Adjusting
the temperature set points on the CS8500 will
put the unit in an override period.
4. Display on Home Screen
Turn ON or OFF for the followings options.
Factory default is set to OFF.
• RTU Fan
• CO value (only on models with CO sensor)
• RTU function state
• Service required alert
Factory default is OFF for all of the above
options. Press < in the upper left-hand corner
of the screen to return to the technician settings
menu.
5. Contractor Info
Information to be completed for this option is
name, address, phone, email and website.
Press < in the upper left-hand corner of the
screen to return to the technician settings
menu.
Temperature Sensor Cong
Temp. Sensor source by default is set to
internal temp. sensor. The other option is
external temp. sensor(s). When external temp.
sensor(s) is selected, the following settings
• Number of external temp. sensor. Default is
1 and up to 9 can be selected.
• Type of external sensor. Options are 10k
sensor type 2 (47W37) or 11k sensor type
type 2.