Table 6. Error Codes and Reminders
Condition Issue Display System Action
Action to Clear / Recovery
Condition
Minor
Outdoor Temperature
(RT17) Sensor
Problem
Outdoor
Temp
Sensor
Displayed on
If measurement of the outdoor
temperature sensor is out of
/ short detection, the alarm
will be activated. Alarm will
automatically clear once in
range condition is detected.
Check sensor and wiring.
Minor
Discharge (Supply) Air
Temperature Sensor
Discharge
Air Temp
Sensor
Displayed on
If measurement of the discharge
air temperature sensor is out
open / short detection, the
alarm will be activated. Alarm
will automatically clear once in
range condition is detected.
Minor
Return Air
Temperature Sensor
Return
Air Temp
Sensor
Displayed on
If measurement of the return
air temperature sensor is out
open / short detection, the
alarm will be activated. Alarm
will automatically clear once in
range condition is detected.
Check sensor and wiring.
Minor
Economizer
Fault
Displayed on
building is not getting the designed
Minor
Too High
Economizer
Fault
Displayed on
Ventilation CFM is too high so
the RTU is wasting energy.