22
•
• Humidify
> Set point - 45% adjustable RH (15 to 45%)
• Dehumidify
> Set point - 50% adjustable RH (35 to 60%)
• Humidify + Dehumidify
Selecting humidify or dehumidify
displays a slider to adjust the desired
levels. Selecting humidify + dehumidify
displays a slider to adjust both levels (hu-
midication-left, dehumidication-right).
Dew point setting is only available with op-
tional remote Outdoor Temperature Sensor
(-15 to 15%, adjustable, 0%).
Normal setting is recommended for mod-
erate climates. Operates the humidier
when there is a call for heating and hu-
midication.
Max setting is recommended for drier
climates. Operates the humidier when
there is a call for humidication only. Over-
cooling range is 0 to 4° degrees.
For dehumidication, the max setting will
overcool the space based on overcool
slider adjustment tool setting.
Ventilation
This option will only appear if a fresh air damper,
ERV or HRV is installed and congured by your in-
staller.