8.
SURVEILLANCEAND
INDICATIONS
The 520
series
has
different
protective
funtions
against
non-permissible operating
states.
If
a
fault
is
displayed,
the controller
is
alvvays
inhibited.
Electrical
Iatching
prevents
an
automatic
reconnection
after
removing
the cause
of
fault.
The
drive
is
enabled
only
after
trip reset.
8.1
TRIP
RESET
Trip
can
only
be
reset
by
disconnecting
and
reconnecting
the
mains.
8.2
SURVEILLANCES
A fault
indication
is
displayed
by
the
LEDs
TRIP and
IMP
(see
8.4.1).
-
Overvoltage
in
the
DC
bus
-
Undervoltage
in
the
DC
bus
-
Overheat
of
heatsink: Heatsink
in
the
area
of
power
semi-conductors
has
exceeded
the
limit
temperature.
-
Short
circuits at
the
outputs A
and
B
-
Earth
fault
protection:
This
function
is
used
to
protect
thetransistor power
stage
when the armature
circuit
has
an
earth
fault.
Warnlnqt
AU
power
terminals
carry
vo~taQe
tip
to
30
seoonds
after
mains
d~soonnection. When
the
mains
is
connected
again
4
LED
±
Wo
must
not
be
illuminated
any
rnore
<after
approx.
30
s~.
otherwise
the
internal
fuse
blow.
~autiow
U
the
LEOs
TRIP
and IMP
are
iuurriinate&
lt
mustbectiecked
in
any
case
If
the
~Jevioehas ~n
earth
fault
in
the
armattire
~ircuit. This
earth
fatilt
mustbe
eiiminat~d1
before
the
device
is
switched
or~
a~ain,
otherwise
Ihe device
rnay
be
damaged!