System bus (CAN) with Ser vo PLC & Drive PLC
Configuration
3-11
l PLC-Systembus EN 1.1
Data transmission limits
The data transmission limits are defined by the number of telegrams per time interval and the data
transmission rate.
You can ascertain these limits when exchanging data in a DC bus connection which includes
only Lenze drive controllers/PLCs by adding code C0361/1 of all participating devices.
Example: Three drive controllers are interconnected via the system bus:
Value of C0361/1 at drive controller 1: 23.5% bus load
Value of C0361/1 at drive controller 2: 12.6% bus load
Value of C0361/1 at drive controller 3: 16.0% bus load
52.1% total bus load
Tip!
The bus load for all participating devices should not exceed 80% .
If other devices are connected, such as decentralised inputs and outputs, their telegrams
must also be taken into account.
A bus overload can, for instance, be caused by the event-controlled transmission of
continuously changing signals.
Remedy:
Change the cycle time setting for CAN2_OUT or CAN3_OUT accordingly so that the total bus
load does not exceed 80 % .