System bus (CAN) with Ser vo PLC & Drive PLC
Configuration (FIF interface)
5-8
l
PLC-Systembus EN 1.1
5.10 Monitoring
5.10.1 Time monitoring for FIF-CAN1_IN ... FIF-CAN3_IN
Via C2457 you can configure a time monitoring for the inputs of process data objects FIF-CAN1_IN
... FIF-CAN3_IN:
Code LCD
Possible settings
Info
Lenze Choice
C2457
1
2
3
CE11monit t ime
CE12monit t ime
CE13monit t ime
3000
3000
3000
0 {1 msec} 65000 Monitoring time for process data
input objects
If there was no telegram received in the defined monitoring time, you can configure the
corresponding reaction in codes C2481 ... C2483:
Code LCD
Possible settings
Info
Lenze Choice
C2481 MONIT CE11 3 0Trip
2 Warning
3Off
Configuration monitoring
FIF-CAN1_IN error (CE11)
C2482 MONIT CE12 3 0Trip
2 Warning
3Off
Configuration monitoring
FIF-CAN2_IN error (CE12)
C2483 MONIT CE13 3 0Trip
2 Warning
3Off
Configuration monitoring
FIF-CAN3_IN error (CE13)
5.10.2 Bus off
If the PLC has decoupled itself from the system bus because too many of the received telegrams
were faulty, the signal “BusOffState” (CE14) is set.
The reaction to this can be configured via code C2484:
Code LCD
Possible settings
Info
Lenze Choice
C2484 MONIT CE14 0 0Off
1 Controller inhibit
2Quickstop
Configuration monitoring
“BusOffState” (CE14)
Tip!
Possible reasons for faulty telegrams may be:
• A missing bus termination
• Insufficient screening
• Potential differences in the grounding of the control electronics
• An excessive bus load. See chapter 3.11.3, “Bus load through the PLC”. (^ 3-10)