System bus (CAN) with Ser vo PLC & Drive PLC
Configuration (FIF interface)
5-5
l PLC-Systembus EN 1.1
5.5 Cycle time (FIF-CAN2_OUT/FIF-CAN3_OUT)
Output data transmission from FIF-CAN2_OUT and FIF-CAN3_OUT can be event or
time-controlled.
The transmission method is configured via code C2456/x:
Code LCD
Possible settings
Info
Lenze Choice
C2456 0 {1} 65000
0 = event-controlled transmission
Task time factor for sending the
process data object.
2
3
CAN2_OUT T
CAN3_OUT T
0
0
FIF-CAN2_OUT
FIF-CAN3_OUT
Event-controlled transmission
C2456/x = 0
The output data is always transmitted when a value has changed in the 8-byte user data
(Lenze default setting).
Time-controlled transmission
C2456/x = 1 ... 65000
The output data is transmitted in the cycle time set in C2456/x (referred to the task cycle
time).
Example:
TheCANobjectisusedina10ms-task.
Factor = 5 set via C2456/2
ðThe CAN object is transmitted every fifth task cycle, i.e. every 50 ms (10 ms x 5).
5.6 Delay time (FIF-CAN2_OUT/FIF-CAN3_OUT)
Via code C2456/4 you can configure a delay time for the transmission of the output data from
FIF-CAN2_OUT and FIF-CAN3_OUT:
Code LCD
Possible settings
Info
Lenze Choice
C2456
4
CAN delay 20
0 {1 msec} 65000 Delay time for the transmission of
the process data object.