System bus (CAN) with Ser vo PLC & Drive PLC
Configuration (FIF interface)
5-4
l
PLC-Systembus EN 1.1
Please ensure that the identifier of the telegram to be transmitted corresponds to the identifier
of the data input object to be addressed.
If the addresses are individually assigned, the identifier for the process data objects is
composed as follows:
Identifier
= 384 +
value from C2454/x
x = subcode
This means that identifiers in the range from 385 ... 896 can be assigned to the process data
objects.
5.4.2 Displaying the set identifier
Via C2455 you can display the identifier set for the process data objects.
C2455 is a display code, you cannot make any settings via C2455.
Code LCD
Possible settings
Info
Lenze Choice
C2455
1
2
3
4
5
6
CAN Id
CAN1_IN Id
CAN1_OUT Id
CAN2_IN Id
CAN2_OUT Id
CAN3_IN Id
CAN3_OUT Id
g
385 {1} 896 System bus identifiers
for the process data objects
FIF-CAN1_IN
FIF-CAN1_OUT
FIF-CAN2_IN
FIF-CAN2_OUT
FIF-CAN3_IN
FIF-CAN3_OUT